-- RPS S.p.A enterprise MIB definition

-- Copyright (c) RPS S.p.A.
-- Version: 1.0.3 by Michele Marcon
-- Date: 29.05.2017

-- Title: RIELLOUPS-MIB

-- RielloUPS-MIB { iso org(3) dod(6) internet(1) private(4)
-- enterprises(1) riello(5491) }

-- ************************************************************************
-- ************************************************************************

RIELLOUPS-MIB DEFINITIONS ::= BEGIN

IMPORTS
       MODULE-IDENTITY, NOTIFICATION-TYPE,
       OBJECT-IDENTITY, Counter32, Gauge32, Integer32
           FROM SNMPv2-SMI
       DisplayString, TimeStamp, TimeInterval, TestAndIncr,
         AutonomousType, TEXTUAL-CONVENTION
           FROM SNMPv2-TC
       MODULE-COMPLIANCE, OBJECT-GROUP
           FROM SNMPv2-CONF
        Gauge, Counter
         FROM RFC1155-SMI
       OBJECT-TYPE
           FROM RFC-1212
       TRAP-TYPE
         FROM RFC-1215
     rielloMIB
             FROM RIELLO-MIB;

rupsMIB              OBJECT IDENTIFIER ::= { rielloMIB 10 }

   PositiveInteger ::= TEXTUAL-CONVENTION
       DISPLAY-HINT "d"
       STATUS       current
       DESCRIPTION
               "This data type is a non-zero and non-negative value."
       SYNTAX       INTEGER (1..2147483647)

   NonNegativeInteger ::= TEXTUAL-CONVENTION
       DISPLAY-HINT "d"
       STATUS       current
       DESCRIPTION
               "This data type is a non-negative value."
       SYNTAX       INTEGER (0..2147483647)


rupsObjects OBJECT IDENTIFIER ::= { rupsMIB  1 }

rupsIdent OBJECT IDENTIFIER ::= { rupsObjects  1 }

rupsIdentManufacturer OBJECT-TYPE
    SYNTAX  DisplayString
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The name of the UPS manufacturer."
    ::= { rupsIdent  1 }

rupsIdentModel OBJECT-TYPE
    SYNTAX  DisplayString
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS Model designation."
    ::= { rupsIdent  2 }

rupsIdentUPSSoftwareVersion OBJECT-TYPE
    SYNTAX  DisplayString
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS firmware/software version(s).  This variable
               may or may not have the same value as
               upsIdentAgentSoftwareVersion in some implementations."
    ::= { rupsIdent  3 }

rupsIdentAgentSoftwareVersion OBJECT-TYPE
    SYNTAX  DisplayString
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS agent software version.  This variable may or
               may not have the same value as
               upsIdentUPSSoftwareVersion in some implementations."
    ::= { rupsIdent  4 }

rupsIdentName OBJECT-TYPE
    SYNTAX  DisplayString
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "A string identifying the UPS.  This object should be
               set by the administrator."
    ::= { rupsIdent  5 }

rupsIdentAttachedDevices OBJECT-TYPE
    SYNTAX  DisplayString
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "A string identifying the devices attached to the
               output(s) of the UPS.  This object should be set by
               the administrator."
    ::= { rupsIdent  6 }
        
rupsIdentIOConfiguration OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS IO configuration."
    ::= { rupsIdent  7 }

rupsIdentUpsType OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS type."
    ::= { rupsIdent  8 }

rupsIdentNominalPowerVA OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS nominal power VA."
    ::= { rupsIdent  9 }

rupsIdentNominalPowerW OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS nominal power W."
    ::= { rupsIdent  10 }

rupsIdentBatteryVoltage OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS nominal battery voltage."
    ::= { rupsIdent  11 }

rupsIdentBatteryCapacity OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS nominal battery capacity."
    ::= { rupsIdent  12 }

rupsIdentOutputVoltage OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS nominal output voltage."
    ::= { rupsIdent  13 }

rupsIdentOutputFrequency OBJECT-TYPE
    SYNTAX  INTEGER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS nominal output frequency."
    ::= { rupsIdent  14 }


rupsBattery OBJECT IDENTIFIER ::= { rupsObjects  2 }

rupsBatteryStatus OBJECT-TYPE
    SYNTAX  INTEGER {
    unknown(1),
    batteryNormal(2),
    batteryLow(3),
    batteryDepleted(4)
}
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The indication of the capacity remaining in the UPS
               system's batteries.   A value of batteryNormal
               indicates that the remaining run-time is greater than
               rupsConfigLowBattTime.  A value of batteryLow indicates
               that the remaining battery run-time is less than or
               equal to rupsConfigLowBattTime.  A value of
               batteryDepleted indicates that the UPS will be unable
               to sustain the present load when and if the utility
               power is lost (including the possibility that the
               utility power is currently absent and the UPS is
               unable to sustain the output)."
    ::= { rupsBattery  1 }

rupsSecondsOnBattery OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS seconds

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "If the unit is on battery power, the elapsed time
               since the UPS last switched to battery power, or the
               time since the network management subsystem was last
               restarted, whichever is less.  Zero shall be returned
               if the unit is not on battery power."
    ::= { rupsBattery  2 }

rupsEstimatedMinutesRemaining OBJECT-TYPE
    SYNTAX  PositiveInteger     -- UNITS minutes

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "An estimate of the time to battery charge depletion
               under the present load conditions if the utility power
               is off and remains off, or if it were to be lost and
               remain off."
    ::= { rupsBattery  3 }

rupsEstimatedChargeRemaining OBJECT-TYPE
    SYNTAX  INTEGER     -- UNITS percent

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "An estimate of the battery charge remaining expressed
               as a percent of full charge."
    ::= { rupsBattery  4 }

rupsBatteryVoltage OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 Volt DC

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present battery voltage."
    ::= { rupsBattery  5 }

rupsBatteryCurrent OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS 0.1 Amp DC

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present battery current."
    ::= { rupsBattery  6 }

rupsBatteryTemperature OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS degrees Centigrade

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The ambient temperature at or near the UPS Battery
               casing."
    ::= { rupsBattery  7 }

rupsBatteryPositiveVoltage OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS V

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS Battery positive voltage."
    ::= { rupsBattery  8 }

rupsBatteryNegativeVoltage OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS V

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS Battery negative voltage."
    ::= { rupsBattery  9 }

rupsBatteryPositiveCurrent OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS 0.1 A

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS Battery positive current."
    ::= { rupsBattery  10 }

rupsBatteryNegativeCurrent OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS 0.1 A

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS Battery positive current."
    ::= { rupsBattery  11 }

rupsIsCharging OBJECT-TYPE
    SYNTAX  INTEGER {
    discharging(0),
    charging(1)
}
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The charging/discharging status of the battery"
    ::= { rupsBattery  12 }

rupsInput OBJECT IDENTIFIER ::= { rupsObjects  3 }

rupsInputLineBads OBJECT-TYPE
    SYNTAX  Counter
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "A count of the number of times the input entered an
               out-of-tolerance condition as defined by the
               manufacturer.  This count is incremented by one each
               time the input transitions from zero out-of-tolerance
               lines to one or more input lines out-of-tolerance."
    ::= { rupsInput  1 }

rupsInputNumLines OBJECT-TYPE
    SYNTAX  NonNegativeInteger
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The number of input lines utilized in this device.
               This variable indicates the number of rows in the
               input table."
    ::= { rupsInput  2 }

rupsInputTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF RUpsInputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of input table entries.  The number of entries
               is given by the value of upsInputNumLines."
    ::= { rupsInput  3 }

rupsInputEntry OBJECT-TYPE
    SYNTAX  RUpsInputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a
               particular input line."
    INDEX   { rupsInputLineIndex }
    ::= { rupsInputTable  1 }

RUpsInputEntry ::=
    SEQUENCE {
        rupsInputLineIndex
            PositiveInteger,

        rupsInputFrequency
            NonNegativeInteger,

        rupsInputVoltage
            NonNegativeInteger,

        rupsInputCurrent
            NonNegativeInteger,

        rupsInputTruePower
            NonNegativeInteger
    }

rupsInputLineIndex OBJECT-TYPE
    SYNTAX  PositiveInteger
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "The input line identifier."
    ::= { rupsInputEntry  1 }

rupsInputFrequency OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 Hertz

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present input frequency."
    ::= { rupsInputEntry  2 }

rupsInputVoltage OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS RMS Volts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present input voltage."
    ::= { rupsInputEntry  3 }

rupsInputCurrent OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 RMS Amp

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present input current."
    ::= { rupsInputEntry  4 }

rupsInputTruePower OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS Watts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present input true power."
    ::= { rupsInputEntry  5 }

rupsOutput OBJECT IDENTIFIER ::= { rupsObjects  4 }

rupsOutputSource OBJECT-TYPE
    SYNTAX  INTEGER {
    other(1),
    none(2),
    normal(3),
    bypass(4),
    battery(5),
    booster(6),
    reducer(7)
}
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present source of output power.  The enumeration
               none(2) indicates that there is no source of output
               power (and therefore no output power), for example,
               the system has opened the output breaker."
    ::= { rupsOutput  1 }

rupsOutputFrequency OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 Hertz

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output frequency."
    ::= { rupsOutput  2 }

rupsOutputNumLines OBJECT-TYPE
    SYNTAX  NonNegativeInteger
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The number of output lines utilized in this device.
               This variable indicates the number of rows in the
               output table."
    ::= { rupsOutput  3 }

rupsOutputTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF RUpsOutputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of output table entries.  The number of
               entries is given by the value of rupsOutputNumLines."
    ::= { rupsOutput  4 }

rupsOutputEntry OBJECT-TYPE
    SYNTAX  RUpsOutputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a
               particular output line."
    INDEX   { rupsOutputLineIndex }
    ::= { rupsOutputTable  1 }

RUpsOutputEntry ::=
    SEQUENCE {
        rupsOutputLineIndex
            PositiveInteger,

        rupsOutputVoltage
            NonNegativeInteger,

        rupsOutputCurrent
            NonNegativeInteger,

        rupsOutputPower
            NonNegativeInteger,

        rupsOutputPercentLoad
            INTEGER,
                        
        rupsOutputPeakCurrent
            NonNegativeInteger
    }

rupsOutputLineIndex OBJECT-TYPE
    SYNTAX  PositiveInteger
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "The output line identifier."
    ::= { rupsOutputEntry  1 }

rupsOutputVoltage OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS RMS Volts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output voltage."
    ::= { rupsOutputEntry  2 }

rupsOutputCurrent OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 RMS Amp

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output current."
    ::= { rupsOutputEntry  3 }

rupsOutputPower OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS Watts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output true power."
    ::= { rupsOutputEntry  4 }

rupsOutputPercentLoad OBJECT-TYPE
    SYNTAX  INTEGER     -- UNITS percent

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The percentage of the UPS power capacity presently
               being used on this output line, i.e., the greater of
               the percent load of true power capacity and the
               percent load of VA."
    ::= { rupsOutputEntry  5 }
        
rupsOutputPeakCurrent OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 RMS Amp

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output peak current."
    ::= { rupsOutputEntry  6 }


rupsBypass OBJECT IDENTIFIER ::= { rupsObjects  5 }

rupsBypassFrequency OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 Hertz

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present bypass frequency."
    ::= { rupsBypass  1 }

rupsBypassNumLines OBJECT-TYPE
    SYNTAX  NonNegativeInteger
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The number of bypass lines utilized in this device.
               This entry indicates the number of rows in the bypass
               table."
    ::= { rupsBypass  2 }

rupsBypassTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF RUpsBypassEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of bypass table entries.  The number of
               entries is given by the value of rupsBypassNumLines."
    ::= { rupsBypass  3 }

rupsBypassEntry OBJECT-TYPE
    SYNTAX  RUpsBypassEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a
               particular bypass input."
    INDEX   { rupsBypassLineIndex }
    ::= { rupsBypassTable  1 }

RUpsBypassEntry ::=
    SEQUENCE {
        rupsBypassLineIndex
            PositiveInteger,

        rupsBypassVoltage
            NonNegativeInteger,

        rupsBypassCurrent
            NonNegativeInteger,

        rupsBypassPower
            NonNegativeInteger
    }

rupsBypassLineIndex OBJECT-TYPE
    SYNTAX  PositiveInteger
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "The bypass line identifier."
    ::= { rupsBypassEntry  1 }

rupsBypassVoltage OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS RMS Volts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present bypass voltage."
    ::= { rupsBypassEntry  2 }

rupsBypassCurrent OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS 0.1 RMS Amp

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present bypass current."
    ::= { rupsBypassEntry  3 }

rupsBypassPower OBJECT-TYPE
    SYNTAX  NonNegativeInteger  -- UNITS Watts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present true power conveyed by the bypass."
    ::= { rupsBypassEntry  4 }

rupsAlarm OBJECT IDENTIFIER ::= { rupsObjects  6 }

rupsAlarmsPresent OBJECT-TYPE
    SYNTAX  Gauge
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present number of active alarm conditions."
    ::= { rupsAlarm  1 }

rupsAlarmTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF RUpsAlarmEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of alarm table entries.  The table contains
               zero, one, or many rows at any moment, depending upon
               the number of alarm conditions in effect.  The table
               is initially empty at agent startup.  The agent
               creates a row in the table each time a condition is
               detected and deletes that row when that condition no
               longer pertains.  The agent creates the first row with
               rupsAlarmId equal to 1, and increments the value of
               rupsAlarmId each time a new row is created, wrapping to
               the first free value greater than or equal to 1 when
               the maximum value of rupsAlarmId would otherwise be
               exceeded.  Consequently, after multiple operations,
               the table may become sparse, e.g., containing entries
               for rows 95, 100, 101, and 203 and the entries should
               not be assumed to be in chronological order because
               rupsAlarmId might have wrapped.

               Alarms are named by an AutonomousType (OBJECT
               IDENTIFIER), rupsAlarmDescr, to allow a single table to
               reflect well known alarms plus alarms defined by a
               particular implementation, i.e., as documented in the
               private enterprise MIB definition for the device.  No
               two rows will have the same value of rupsAlarmDescr,
               since alarms define conditions.  In order to meet this
               requirement, care should be taken in the definition of
               alarm conditions to insure that a system cannot enter
               the same condition multiple times simultaneously.

               The number of rows in the table at any given time is
               reflected by the value of rupsAlarmsPresent."
    ::= { rupsAlarm  2 }

rupsAlarmEntry OBJECT-TYPE
    SYNTAX  RUpsAlarmEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a





               particular alarm."
    INDEX   { rupsAlarmId }
    ::= { rupsAlarmTable  1 }

RUpsAlarmEntry ::=
    SEQUENCE {
        rupsAlarmId
            PositiveInteger,

        rupsAlarmDescr
            OBJECT IDENTIFIER,

        rupsAlarmTime
            PositiveInteger
    }

rupsAlarmId OBJECT-TYPE
    SYNTAX  PositiveInteger
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A unique identifier for an alarm condition.  This
               value must remain constant."
    ::= { rupsAlarmEntry  1 }

rupsAlarmDescr OBJECT-TYPE
    SYNTAX  OBJECT IDENTIFIER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "A reference to an alarm description object.  The
               object referenced should not be accessible, but rather
               be used to provide a unique description of the alarm
               condition."
    ::= { rupsAlarmEntry  2 }

rupsAlarmTime OBJECT-TYPE
    SYNTAX  PositiveInteger
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The value of sysUpTime when the alarm condition was
               detected.  If the alarm condition was detected at the
               time of agent startup and presumably existed before
               agent startup, the value of rupsAlarmTime shall equal
               0."
    ::= { rupsAlarmEntry  3 }

rupsWellKnownAlarms OBJECT IDENTIFIER ::= { rupsAlarm  3 }

rupsAlarmBatteryBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  1 }

rupsAlarmOnBattery OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  2 }

rupsAlarmLowBattery OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  3 }

rupsAlarmShutdownImminent OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  4 }

rupsAlarmTempBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  5 }

rupsAlarmFault OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  6 }

rupsAlarmInternal OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  7 }

rupsAlarmOutputOverload OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  8 }

rupsAlarmOnBypass OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  9 }

rupsAlarmBypassBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  10 }

rupsAlarmShutdownImminent OBJECT IDENTIFIER ::= { rupsWellKnownAlarms  11 }

   --
   -- The Test Group
   --

   rupsTest               OBJECT IDENTIFIER ::= { rupsObjects 7 }

   rupsTestId OBJECT-TYPE
       SYNTAX     OBJECT IDENTIFIER
       ACCESS read-write
       STATUS     optional
       DESCRIPTION
               "The test is named by an OBJECT IDENTIFIER which
               allows a standard mechanism for the initiation of
               tests, including the well known tests identified in
               this document as well as those introduced by a
               particular implementation, i.e., as documented in the
               private enterprise MIB definition for the device.

               Setting this variable initiates the named test. Sets
               to this variable require the presence of
               upsTestSpinLock in the same SNMP message.

               The set request will be rejected with an appropriate
               error message if the requested test cannot be
               performed, including attempts to start a test when
               another test is already in progress.  The status of
               the current or last test is maintained in
               upsTestResultsSummary. Tests in progress may be
               aborted by setting the rupsTestId variable to
               rupsTestAbortTestInProgress.

               Read operations return the value of the name of the
               test in progress if a test is in progress or the name
               of the last test performed if no test is in progress,
               unless no test has been run, in which case the well
               known value upsTestNoTestsInitiated is returned."
       ::= { rupsTest 1 }

   -- see [6] for more information on the semantics of objects with
   -- syntax of TestAndIncr

   rupsTestSpinLock OBJECT-TYPE
       SYNTAX     TestAndIncr
       ACCESS read-write
       STATUS     optional
       DESCRIPTION
               "A spin lock on the test subsystem.  The spinlock is
               used as follows.

               Before starting a test, a manager-station should make
               sure that a test is not in progress as follows:

                   try_again:
                     get (upsTestSpinLock)
                     while (upsTestResultsSummary == inProgress) {
                       /* loop while a test is running for another
               manager */
                       short delay
                       get (upsTestSpinLock)
                     }
                     lock_value = upsTestSpinLock
                     /* no test in progress, start the test */
                     set (upsTestSpinLock = lock_value, upsTestId =
               requested_test)
                     if (error_index == 1) { /* (upsTestSpinLock
               failed) */
                       /* if problem is not access control, then
                           some other manager slipped in ahead of us
               */
                       goto try_again
                     }
                     if (error_index == 2) { /* (upsTestId) */
                       /* cannot perform the test */
                       give up
                     }
                     /* test started ok */
                     /* wait for test completion by polling
               upsTestResultsSummary */
                     get (upsTestSpinLock, upsTestResultsSummary,
               upsTestResultsDetail)
                     while (upsTestResultsSummary == inProgress) {
                       short delay
                       get (upsTestSpinLock, upsTestResultsSummary,
               upsTestResultsDetail)
                     }
                     /* when test completes, retrieve any additional
               test results */
                     /* if upsTestSpinLock == lock_value + 1, then
               these are our test */
                     /* results (as opposed to another manager's */
                     The initial value of upsTestSpinLock at agent
               initialization shall
                     be 1."
       ::= { rupsTest 2 }

   rupsTestResultsSummary OBJECT-TYPE
       SYNTAX     INTEGER {
           donePass(1),
           doneWarning(2),
           doneError(3),
           aborted(4),
           inProgress(5),
           noTestsInitiated(6)
       }
       ACCESS read-only
       STATUS     optional
       DESCRIPTION
               "The results of the current or last UPS diagnostics
               test performed.  The values for donePass(1),
               doneWarning(2), and doneError(3) indicate that the
               test completed either successfully, with a warning, or
               with an error, respectively.  The value aborted(4) is
               returned for tests which are aborted by setting the
               value of upsTestId to upsTestAbortTestInProgress.
               Tests which have not yet concluded are indicated by
               inProgress(5).  The value noTestsInitiated(6)
               indicates that no previous test results are available,
               such as is the case when no tests have been run since
               the last reinitialization of the network management
               subsystem and the system has no provision for non-
               volatile storage of test results."
       ::= { rupsTest 3 }

   rupsTestResultsDetail OBJECT-TYPE
       SYNTAX     DisplayString (SIZE (0..255))
       ACCESS read-only
       STATUS     optional
       DESCRIPTION
               "Additional information about upsTestResultsSummary.
               If no additional information available, a zero length
               string is returned."
       ::= { rupsTest 4 }

   rupsTestStartTime OBJECT-TYPE
       SYNTAX     TimeStamp
       ACCESS read-only
       STATUS     optional
       DESCRIPTION
               "The value of sysUpTime at the time the test in
               progress was initiated, or, if no test is in progress,
               the time the previous test was initiated.  If the
               value of upsTestResultsSummary is noTestsInitiated(6),
               upsTestStartTime has the value 0."
       ::= { rupsTest 5 }

   rupsTestElapsedTime OBJECT-TYPE
       SYNTAX     TimeInterval
       ACCESS read-only
       STATUS     optional
       DESCRIPTION
               "The amount of time, in TimeTicks, since the test in
               progress was initiated, or, if no test is in progress,
               the previous test took to complete.  If the value of
               upsTestResultsSummary is noTestsInitiated(6),
               upsTestElapsedTime has the value 0."
       ::= { rupsTest 6 }

   --
   -- Well known tests.
   --

   rupsWellKnownTests     OBJECT IDENTIFIER ::= { rupsTest 7 }


   rupsTestNoTestsInitiated OBJECT IDENTIFIER
   --            "No tests have been initiated and no test is in
   --            progress."
       ::= { rupsWellKnownTests  1 }

   rupsTestAbortTestInProgress OBJECT IDENTIFIER
   --            "The test in progress is to be aborted / the test in
   --            progress was aborted."
       ::= { rupsWellKnownTests  2 }

   rupsTestGeneralSystemsTest OBJECT IDENTIFIER
   --            "The manufacturer's standard test of UPS device
   --            systems."
       ::= { rupsWellKnownTests  3 }

   rupsTestQuickBatteryTest OBJECT IDENTIFIER
   --            "A test that is sufficient to determine if the battery
   --            needs replacement."
       ::= { rupsWellKnownTests  4 }

   rupsTestDeepBatteryCalibration OBJECT IDENTIFIER
   --            "The system is placed on battery to a discharge level,
   --            set by the manufacturer, sufficient to determine
   --            battery replacement and battery run-time with a high
   --            degree of confidence.  WARNING:  this test will leave
   --            the battery in a low charge state and will require
   --            time for recharging to a level sufficient to provide
   --            normal battery duration for the protected load."
       ::= { rupsWellKnownTests  5 }

rupsControl OBJECT IDENTIFIER ::= { rupsObjects  8 }

rupsShutdownType OBJECT-TYPE
    SYNTAX  INTEGER {
    output(1),
    system(2)
}
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "This object determines the nature of the action to be
               taken at the time when the countdown of the





               upsShutdownAfterDelay and upsRebootWithDuration
               objects reaches zero.

               Setting this object to output(1) indicates that
               shutdown requests should cause only the output of the
               UPS to turn off.  Setting this object to system(2)
               indicates that shutdown requests will cause the entire
               UPS system to turn off."
    ::= { rupsControl  1 }

rupsShutdownAfterDelay OBJECT-TYPE
    SYNTAX  INTEGER     -- UNITS seconds

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object will shutdown (i.e., turn off)
               either the UPS output or the UPS system (as determined
               by the value of upsShutdownType at the time of
               shutdown) after the indicated number of seconds, or
               less if the UPS batteries become depleted. Setting
               this object to 0 will cause the shutdown to occur
               immediately.  Setting this object to -1 will abort the
               countdown.  If the system is already in the desired
               state at the time the countdown reaches 0, then
               nothing will happen.  That is, there is no additional
               action at that time if upsShutdownType = system and
               the system is already off.  Similarly, there is no
               additional action at that time if upsShutdownType =
               output and the output is already off.  When read,
               upsShutdownAfterDelay will return the number of
               seconds remaining until shutdown, or -1 if no shutdown
               countdown is in effect.  On some systems, if the agent
               is restarted while a shutdown countdown is in effect,
               the countdown may be aborted.  Sets to this object
               override any upsShutdownAfterDelay already in effect."
    ::= { rupsControl  2 }

rupsStartupAfterDelay OBJECT-TYPE
    SYNTAX  INTEGER     -- UNITS seconds

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object will start the output after the
               indicated number of seconds, including starting the
               UPS, if necessary.  Setting this object to 0 will
               cause the startup to occur immediately.  Setting this





               object to -1 will abort the countdown.  If the output
               is already on at the time the countdown reaches 0,
               then nothing will happen.  Sets to this object
               override the effect of any upsStartupAfterDelay
               countdown or upsRebootWithDuration countdown in
               progress.  When read, upsStartupAfterDelay will return
               the number of seconds until startup, or -1 if no
               startup countdown is in effect.  If the countdown
               expires during a utility failure, the startup shall
               not occur until the utility power is restored.  On
               some systems, if the agent is restarted while a
               startup countdown is in effect, the countdown is
               aborted."
    ::= { rupsControl  3 }

rupsRebootWithDuration OBJECT-TYPE
    SYNTAX  INTEGER     -- UNITS seconds

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object will immediately shutdown (i.e.,
               turn off) either the UPS output or the UPS system (as
               determined by the value of upsShutdownType at the time
               of shutdown) for a period equal to the indicated
               number of seconds, after which time the output will be
               started, including starting the UPS, if necessary.  If
               the number of seconds required to perform the request
               is greater than the requested duration, then the
               requested shutdown and startup cycle shall be
               performed in the minimum time possible, but in no case
               shall this require more than the requested duration
               plus 60 seconds.  When read, upsRebootWithDuration
               shall return the number of seconds remaining in the
               countdown, or -1 if no countdown is in progress.  If
               the startup should occur during a utility failure, the
               startup shall not occur until the utility power is
               restored."
    ::= { rupsControl  4 }

rupsAutoRestart OBJECT-TYPE
    SYNTAX  INTEGER {
    on(1),
    off(2)
}
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object to 'on' will cause the UPS system
               to restart after a shutdown if the shutdown occurred
               during a power loss as a result of either a
               upsShutdownAfterDelay or an internal battery depleted
               condition.  Setting this object to 'off' will prevent
               the UPS system from restarting after a shutdown until
               an operator manually or remotely explicitly restarts
               it.  If the UPS is in a startup or reboot countdown,
               then the UPS will not restart until that delay has
               been satisfied."
    ::= { rupsControl  5 }

rupsTemperature OBJECT IDENTIFIER ::= { rupsObjects  10 }
        
rupsSystemTemperature OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  1 }

rupsPowerTemperature1 OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  2 }
        
rupsPowerTemperature2 OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  3 }
        
rupsPowerTemperature3 OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  4 }
        
rupsChargerTemperature OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  5 }
        
rupsBatteryPositiveTemperature OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  6 }
        
rupsBatteryNegativeTemperature OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  7 }
        
rupsBatteryExternalTemperature OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS degree Celsius

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present temperature."
    ::= { rupsTemperature  8 }

rupsMPS OBJECT IDENTIFIER ::= { rupsObjects  20 }       

mpsAlarmGroupS OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group s."
    ::= { rupsMPS  1 }
        
mpsAlarmGroupC OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group c."
    ::= { rupsMPS  2 }
        
mpsAlarmGroupB OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group b."
    ::= { rupsMPS  3 }
        
mpsAlarmGroupR OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group r."
    ::= { rupsMPS  4 }
        
mpsAlarmGroupRI OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group RI."
    ::= { rupsMPS  5 }
        
mpsAlarmGroupI OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group I."
    ::= { rupsMPS  6 }
        
mpsAlarmGroupA0 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group A0."
    ::= { rupsMPS  7 }
        
mpsAlarmGroupA1 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group A1."
    ::= { rupsMPS  8 }
        
mpsAlarmGroupA2 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group A2."
    ::= { rupsMPS  9 }
        
mpsAlarmGroupA3 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group A3."
    ::= { rupsMPS  10 }
        
mpsAlarmGroupA4 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group A4."
    ::= { rupsMPS  11 }
        
mpsAlarmGroupA5 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The alarm group A5."
    ::= { rupsMPS  12 }

rupsMST OBJECT IDENTIFIER ::= { rupsObjects  21 }       

mstWarningGroupW0W1 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The anomaly group W0W1."
    ::= { rupsMST  1 }
        
mstAnomalyGroupA0A1 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The anomaly group A0A1."
    ::= { rupsMST  2 }
        
mstAnomalyGroupA2A3 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The anomaly group A2A3."
    ::= { rupsMST  3 }
        
mstAnomalyGroupA4A5 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The anomaly group A4A5."
    ::= { rupsMST  4 }
        
mstFaultGroupF0F1 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The fault group F0F1."
    ::= { rupsMST  5 }
        
mstFaultGroupF2F3 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The fault group F2F3."
    ::= { rupsMST  6 }
        
mstFaultGroupF4F5 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The fault group F4F5."
    ::= { rupsMST  7 }
        
mstLockGroupL0L1 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The lock group L0L1."
    ::= { rupsMST  8 }
        
mstLockGroupL2L3 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The lock group L2L3."
    ::= { rupsMST  9 }
        
mstLockGroupL4L5 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The lock group L4L5."
    ::= { rupsMST  10 }
        
mstEventGroupE0E1 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The event group E0E1."
    ::= { rupsMST  11 }
        
rupsMPW OBJECT IDENTIFIER ::= { rupsObjects  22 }       

mpwSystemStatusGroup1 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The system status group 1."
    ::= { rupsMPW  1 }
        
mpwSystemStatusGroup2 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The system status group 2."
    ::= { rupsMPW  2 }
        
mpwSystemStatusGroup3 OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The system status group 3."
    ::= { rupsMPW  3 }
        
mpwBypassModuleAlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The bypass module alarm group."
    ::= { rupsMPW  4 }
        
mpwPowerModule1AlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The power module 1 alarm group."
    ::= { rupsMPW  5 }
        
mpwPowerModule2AlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The power module 2 alarm group."
    ::= { rupsMPW  6 }
        
mpwPowerModule3AlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The power module 3 alarm group."
    ::= { rupsMPW  7 }
        
mpwPowerModule4AlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The power module 4 alarm group."
    ::= { rupsMPW  8 }
        
mpwPowerModule5AlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The power module 5 alarm group."
    ::= { rupsMPW  9 }
        
mpwPowerModule6AlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The power module 6 alarm group."
    ::= { rupsMPW  10 }
        
mpwPowerModule7AlarmGroup OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The power module 7 alarm group."
    ::= { rupsMPW  11 }
        
mpwBypassModuleStatus OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The bypass module status."
    ::= { rupsMPW  12 }
        
mpwPowerModule1Status OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The status of power module 1."
    ::= { rupsMPW  13 }
        
mpwPowerModule2Status OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The status of power module 2."
    ::= { rupsMPW  14 }
        
mpwPowerModule3Status OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The status of power module 3."
    ::= { rupsMPW  15 }
        
mpwPowerModule4Status OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The status of power module 4."
    ::= { rupsMPW  16 }
        
mpwPowerModule5Status OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The status of power module 5."
    ::= { rupsMPW  17 }
        
mpwPowerModule6Status OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The status of power module 6."
    ::= { rupsMPW  18 }
        
mpwPowerModule7Status OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The status of power module 7."
    ::= { rupsMPW  19 }
        
mpwControl OBJECT IDENTIFIER ::= { rupsMPW  20 }

mpwCommandCode OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Command code."
    ::= { mpwControl  1 }

mpwShutdownDelay OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Shutdown delay."
    ::= { mpwControl  2 }

mpwRestoreDelay OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Restore delay."
    ::= { mpwControl  3 }

mpwModuleApplyCommand OBJECT-TYPE
    SYNTAX  INTEGER

    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Module apply command"
    ::= { mpwControl  4 }

mpwCommandResult OBJECT-TYPE
    SYNTAX  INTEGER  -- UNITS RMS Volts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "Result of command."
    ::= { mpwControl  5 }

        
rupsTraps OBJECT IDENTIFIER ::= { rupsMIB  2 }

rupsTrapOnBattery TRAP-TYPE
    ENTERPRISE  rupsTraps
    VARIABLES   { rupsEstimatedMinutesRemaining,  rupsSecondsOnBattery,
rupsConfigLowBattTime }
    DESCRIPTION
           "The UPS is operating on battery power.  This trap is
               persistent and is resent at one minute intervals until
               the UPS either turns off or is no longer running on
               battery."
    ::= 1

rupsTrapTestCompleted TRAP-TYPE
    ENTERPRISE  rupsTraps
    DESCRIPTION
           "This trap is sent upon completion of a UPS diagnostic
               test."
    ::= 2

rupsTrapAlarmEntryAdded TRAP-TYPE
    ENTERPRISE  rupsTraps
    DESCRIPTION
           "This trap is sent each time an alarm is inserted into
               to the alarm table.  It is sent on the insertion of

               all alarms except for rupsAlarmOnBattery and
               rupsAlarmTestInProgress."
    ::= 3

rupsTrapAlarmEntryRemoved TRAP-TYPE
    ENTERPRISE  rupsTraps
    DESCRIPTION
           "This trap is sent each time an alarm is removed from
               the alarm table.  It is sent on the removal of all
               alarms except for rupsAlarmTestInProgress."
    ::= 4


END

